12345 Sample St Report

This is a sample report. This sample report is composed from several inspections and is not an actual report. The purpose of this sample report is to give the viewer an idea of how a typical home inspection report looks. The report layout, style, quality of the photos/videos and content are similar to the reports that are sent to the customer. The summary contains the key deficiencies that buyers tend to focus on.

 

Table of Contents

General Info

Property Address
12345 Sample St
Sample City FL 12345
Date of Inspection
2/26/2021
Report ID
12345022621
Customer(s)
John Doe
Time of Inspection
09:00 AM
Real Estate Agent

Inspection Details
In Attendance:
Customer
Type of building:
Single Family (2 story)
Approximate age of building:
Under 10 Years
Temperature:
Over 65 (F) = 18 (C)
Weather:
Clear
Ground/Soil surface condition:
Dry
Rain in last 3 days:
No
Radon Test:
No
Water Test:
No
Comment Key & Definitions

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home.
Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further
inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for
normal wear and tear.

Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason
for not inspecting.

Not Present (NP) = This item, component or unit is not in this home or building.

Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or
units that can be repaired to satisfactory condition may not need replacement.

 

1. Roofing

The inspector shall inspect from ground level or eaves: The roof covering. The gutters. The downspouts. The vents, flashings, skylights, chimney and other roof penetrations. The general structure
of the roof from the readily accessible panels, doors or stairs.The inspector is not required to: Walk on any roof surface, predict the service life expectancy, inspect underground downspout diverter drainage pipes, remove snow, ice, debris or other conditions
that prohibit the observation of the roof surfaces, move insulation, inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similar attachments. Walk on any roof areas that appear,
in the opinion of the inspector to be unsafe, and or cause damage. Perform a water test, warrant or certify the roof. Confirm proper fastening or installation of any roof material.
Styles & Materials
Roof Covering:
3-Tab fiberglass
Viewed roof covering from:
Walked roof
Camera Pole
Sky Light(s):
None
Chimney (exterior):
N/A

 

IN

NI

NP

RR

1.0

Roof Coverings

1.1

Flashings

1.2

Skylights, Chimneys and Roof Penetrations

1.3

Roof Drainage Systems

IN

NI

NP

RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

Comments:

1.0 (1)
At the time of inspection the roof covering had excessive granule loss on the entire roof. No active leaks were found. I recommend repair/replace as needed.

1.0 Item 1 (Picture)

1.0 Item 2 (Picture)
1.0 (2)
The roof covering is missing the vent pipes. Plumbing drain/waste vents are required for proper water flow drainage in the plumbing systems. A qualified contractor should
inspect and repair as needed.

1.0 Item 3 (Picture)
The roof of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Roof coverings and
skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector has your best
interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it
relates to the comments in this inspection report.

 

2. Exterior

The inspector shall inspect: The siding, flashing and trim. All exterior doors, decks, stoops, steps, stairs, porches, railings, eaves, soffits and fascias. And report as in need of repair any spacing between intermediate balusters, spindles, or rails for steps, stairways, balconies, and railings that permit the passage of an object greater than four inches in diameter. A representative number of windows. The vegetation, surface drainage and retaining walls when these are likely to adversely affect the structure. And describe the exterior wall covering.

The inspector is not required to: Inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, or exterior accent lighting, Inspect items, including window and door flashings, which are not visible or readily accessible from the ground, Inspect geological, geotechnical, hydrological and/or soil conditions, Inspect recreational facilities, playground equipment. Inspect seawalls, break-walls and docks, Inspect erosion control and earth stabilization measures, Inspect for safety type glass, Inspect underground utilities, Inspect underground items, Inspect wells or springs, Inspect solar, wind or geothermal systems, Inspect swimming pools or spas, Inspect wastewater treatment systems septic systems or cesspools, Inspect irrigation or sprinkler systems, Inspect drain fields or drywells, Determine the integrity of multi-pane window glazing or the thermal window seals.

Styles & Materials
Siding Style:
Lap
Cement stucco
Siding Material:
Vinyl
Cement Stucco
Exterior Entry Doors:
Steel
Appurtenance:
Porch
Driveway:
Concrete

 

IN

NI

NP

RR

2.0

Wall Cladding Flashing and Trim

2.1

Doors (Exterior)

2.2

Windows

2.3

Decks, Balconies, Stoops, Steps, Areaways, Porches, Patio/Cover and Applicable Railings

2.4

Vegetation, Grading, Drainage, Driveways, Patio Floor, Walkways and Retaining Walls (With respect to their effect on the condition of the building)

2.5

Eaves, Soffits and Fascias

IN

NI

NP

RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

Comments:

2.0
There were sections of vinyl siding and water barrier house wrap at the rear of home that were missing or incomplete at time of inspection. Deterioration can eventually
occur if not corrected. A qualified person should repair or replace as needed.

2.0 Item 1 (Picture)
The exterior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

 

3. Structural Components

The inspector shall inspect: The basement. The foundation. The crawlspace. The visible structural components. Any present conditions or clear indications of active water penetration observed by the inspector. And report any general indications of foundation movement that are observed by the inspector, such as but not limited to sheetrock cracks, brick cracks, out-of-square door frames or floor slopes.

The inspector is not required to: Enter any crawlspaces that are not readily accessible or where entry could cause damage or pose a hazard to the inspector, Move stored items or debris, Operate sump pumps with inaccessible floats, Identify size, spacing, span, location or determine adequacy of foundation bolting, bracing, joists, joist spans or support systems, Provide any engineering or architectural service, Report on the adequacy of any structural system or component.

Styles & Materials
Foundation:
Poured concrete
Method used to observe Crawlspace:
Crawled
Robot Crawler
Floor Structure:
2 X 10
Wall Structure:
2 X 4 Wood
Ceiling Structure:
2X4
Roof Structure:
Engineered wood trusses
Roof-Type:
Gable
Method used to observe attic:
Walked
Attic info:
Attic access

 

IN

NI

NP

RR

3.0

Foundations, Basement and Crawlspace (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.)

3.1

Walls (Structural)

3.2

Columns or Piers

3.3

Floors (Structural)

3.4

Ceilings (Structural)

3.5

Roof Structure and Attic

IN

NI

NP

RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

 

The structure of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

4. Heating / Central Air Conditioning

The inspector shall inspect: The heating system and describe the energy source and heating method using normal operating controls. And report as in need of repair electric furnaces which do not operate. And report if inspector deemed the furnace inaccessible. The central cooling equipment using normal operating controls. The fireplace, and open and close the damper door if readily accessible and operable. Hearth extensions and other permanently installed components. And report as in need of repair deficiencies in the lintel, hearth and material surrounding the fireplace, including clearance from combustible materials.

The inspector is not required to: Inspect or evaluate interiors of flues or chimneys, fire chambers, heat exchangers, humidifiers, dehumidifiers, electronic air filters, solar heating systems, solar heating systems or fuel tanks. Inspect underground fuel tanks. Determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the heating system. Light or ignite pilot flames. Activate heating, heat pump systems, or other heating systems when ambient temperatures or when other circumstances are not conducive to safe operation or may damage the equipment. Override electronic thermostats. Evaluate fuel quality. Verify thermostat calibration, heat anticipation or automatic setbacks, timers, programs or clocks. Determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the cooling system. Inspect window units, through-wall units, or electronic air filters. Operate equipment or systems if exterior temperature is below 60 degrees Fahrenheit or when other circumstances are not conducive to safe operation or may damage the equipment. Inspect or determine thermostat calibration, heat anticipation or automatic setbacks or clocks. Examine electrical current, coolant fluids or gasses, or coolant leakage. Inspect the flue or vent system. Inspect the interior of chimneys or flues, fire doors or screens, seals or gaskets, or mantels. Determine the need for a chimney sweep. Operate gas fireplace inserts. Light pilot flames. Determine the appropriateness of such installation. Inspect automatic fuel feed devices. Inspect combustion and/or make-up air devices. Inspect heat distribution assists whether gravity controlled or fan assisted. Ignite or extinguish fires. Determine draft characteristics. Move fireplace inserts, stoves, or firebox contents. Determine adequacy of draft, perform a smoke test or dismantle or remove any component. Perform an NFPA inspection. Perform a Phase 1 fireplace and chimney inspection.

Styles & Materials
Heat Type:
Electric heat
Energy Source:
Electric
Number of Heat Systems (excluding wood):
One
Heat System Brand:
CARRIER
Ductwork:
Insulated
Filter Type:
Disposable
Filter Size:
16×20
Types of Fireplaces:
None
Cooling Equipment Type:
Air conditioner unit
Cooling Equipment Energy Source:
Electricity
Number of AC Only Units:
One
Central Air Brand:
CARRIER
Condenser Unit Model Number:
Model number
Extra Info : 25HBC560A300
Condenser Unit Serial Number:
Serial Number
Extra Info : 3920F18491
Air Handler Model Number:
Model Number
Extra Info : FX4DNF061
Air Handler Serial Number:
Serial Number
Extra Info : 3920F18491

 

IN

NI

NP

RR

4.0

Heating Equipment

4.1

Normal Operating Controls

4.2

Automatic Safety Controls

4.3

Distribution Systems (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)

4.4

Presence of Installed Heat Source in Each Room

4.5

Chimneys, Flues and Vents (for fireplaces, gas water heaters or heat systems)

4.6

Cooling and Air Handler Equipment

4.7

Normal Operating Controls

4.8

Presence of Installed Cooling Source in Each Room

IN

NI

NP

RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

Comments:

4.4
The HVAC heating system was in working order at the time of inspection.

4.4 Item 1 (Picture)

4.4 Item 2 (Picture)
4.5
The vent pipe for gas furnace is missing a section in the attic allowing carbon monoxide into area. This is a critical safety issue and should be repaired. I recommend a
qualified licensed heat contractor inspect further and repair as needed.

4.5 Item 1 (Picture)
4.8
The HVAC cooling system was in working order. There was a 17 degree temperature split recorded at the time of inspection. This is well within the normal range.

4.8 Item 1 (Picture)

4.8 Item 2 (Picture)
The heating and cooling system of this home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

 

5. Plumbing System

The inspector shall: Verify the presence of and identify the location of the main water shutoff valve. Inspect the water heating equipment, including combustion air, venting, connections, energy sources, seismic bracing, and verify the presence or absence of temperature-pressure relief valves and/or Watts 210 valves. Flush toilets. Run water in sinks, tubs, and showers. Inspect the interior water supply including all fixtures and faucets. Inspect the drain, waste and vent systems, including all fixtures. Describe any visible fuel storage systems. Inspect the drainage sump pumps testing sumps with accessible floats. Inspect and describe the water supply, drain, waste and main fuel shut-off valves, as well as the location of the water main and main fuel shut-off valves. Inspect and determine if the water supply is public or private. Inspect and report as in need of repair deficiencies in the water supply by viewing the functional flow in two fixtures operated simultaneously. Inspect and report as in need of repair deficiencies in installation and identification of hot and cold faucets. Inspect and report as in need of repair mechanical drain-stops that are missing or do not operate if installed in sinks, lavatories and tubs. Inspect and report as in need of repair commodes that have cracks in the ceramic material, are improperly mounted on the floor, leak, or have tank components which do not operate.

The inspector is not required to: Light or ignite pilot flames. Determine the size, temperature, age, life expectancy or adequacy of the water heater. Inspect interiors of flues or chimneys, water softening or filtering systems, well pumps or tanks, safety or shut-of valves, floor drains, lawn sprinkler systems or fire sprinkler systems. Determine the exact flow rate, volume, pressure, temperature, or adequacy of the water supply. Determine the water quality or potability or the reliability of the water supply or source. Open sealed plumbing access panels. Inspect clothes washing machines or their connections. Operate any main, branch or fixture valve. Test shower pans, tub and shower surrounds or enclosures for leakage. Evaluate the compliance with local or state conservation or energy standards, or the proper design or sizing of any water, waste or venting components, fixtures or piping. Determine the effectiveness of anti-siphon, back-flow prevention or drain-stop devices. Determine whether there are sufficient clean-outs for effective cleaning of drains. Evaluate gas, liquid propane or oil storage tanks. Inspect any private sewage waste disposal system or component of. Inspect water treatment systems or water filters. Inspect water storage tanks, pressure pumps or bladder tanks. Evaluate time to obtain hot water at fixtures, or perform testing of any kind to water heater elements. Evaluate or determine the adequacy of combustion air. Test, operate, open or close safety controls, manual stop valves and/or temperature or pressure relief valves. Examine ancillary systems or components, such as, but not limited to, those relating to solar water heating, hot water circulation.

Styles & Materials
Water Source:
Well
Water Filters:
None
Plumbing Water Supply (into home):
PVC
Plumbing Water Distribution (inside home):
CPVC
Washer Drain Size:
2″ Diameter
Plumbing Waste:
PVC
Water Heater Power Source:
Electric
Water Heater Capacity:
50 Gallon (2-3 people)
Water Heater Location:
Garage
WH Manufacturer:
A.O. SMITH
Water Heater Model Number:
Model Number
Extra Info : ENT-50 130
Water Heater Serial Number:
Serial Number
Extra Info : 2048122057055

IN

NI

NP

RR

5.0

Plumbing Drain, Waste and Vent Systems

5.1

Plumbing Water Supply, Distribution System and Fixtures

5.2

Hot Water Systems, Controls, Chimneys, Flues and Vents

5.3

Main Water Shut-off Device (Describe location)

IN

NI

NP

RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

Comments:

5.0
The plumbing waste line for the hall bath tub and hall bath sink leaks in the crawlspace. Repairs are needed to prevent waste water from continuing to leak into crawlspace.
A qualified person should repair as necessary.

5.0 Item 1 (Picture)

5.0 Item 2 (Picture)

5.0 Item 3 (Picture)
5.1 (1)
The water pressure was recorded at 44 PSI at the time of inspection.

5.1 Item 1 (Picture)
5.1 (2)
The sink faucet leaks leaks at the master bath. Repairs are needed to stop leaking water from damaging the cabinet bottom. A qualified person should repair as
necessary.

5.1 Item 2 (Picture)
5.1 Item 3 (Video)
5.1 (3)
The cold supply valve is leaking and has damaged the drywall behind the wash machine. I recommend repair or replace as needed.

5.1 Item 4 (Picture)
5.2
The water temperature of the hot water supply was recorded at 116-119 degrees. This is well within the safe range.

5.2 Item 1 (Picture)

5.2 Item 2 (Picture)

5.2 Item 3 (Picture)

5.2 Item 4 (Picture)

5.2 Item 5 (Picture)

5.2 Item 6 (Picture)

 

5.3
The main water shut off valve is located on the North East exterior corner of the home.

5.3 Item 1 (Picture)
The plumbing in the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

 

6. Electrical System

The inspector shall inspect: The service line. The meter box. The main disconnect. And determine the rating of the service amperage. Panels, breakers and fuses. The service grounding and bonding. A representative sampling of switches, receptacles, light fixtures, AFCI receptacles and test all GFCI receptacles and GFCI circuit breakers observed and deemed to be GFCI’s during the inspection. And report the presence of solid conductor aluminum branch circuit wiring if readily visible. And report on any GFCI-tested receptacles in which power is not present, polarity is incorrect, the receptacle is not grounded, is not secured to the wall, the cover is not in place, the ground fault circuit interrupter devices are not properly installed or do not operate properly, or evidence of arcing or excessive heat is present. The service entrance conductors and the condition of their sheathing. The ground fault circuit interrupters observed and deemed to be GFCI’s during the inspection with a GFCI tester. And describe the amperage rating of the service. And report the absence of smoke detectors. Service entrance cables and report as in need of repair deficiencies in the integrity of the insulation, drip loop, or separation of conductors at weatherheads and clearances.

The inspector is not required to: Insert any tool, probe or device into the main panel, sub-panels, downstream panel, or electrical fixtures. Operate electrical systems that are shut down. Remove panel covers or dead front covers if not readily accessible. Operate over current protection devices. Operate non-accessible smoke detectors. Measure or determine the amperage or voltage of the main service if not visibly labeled. Inspect the alarm system and components. Inspect the ancillary wiring or remote control devices. Activate any electrical systems or branch circuits which are not energized. Operate overload devices. Inspect low voltage systems, electrical de-icing tapes, swimming pool wiring or any time-controlled devices. Verify the continuity of the connected service ground. Inspect private or emergency electrical supply sources, including but not limited to generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility. Inspect spark or lightning arrestors. Conduct voltage drop calculations. Determine the accuracy of breaker labeling. Inspect exterior lighting.

Styles & Materials
Electrical Service Conductors:
Below ground
Panel Capacity:
200 AMP
Panel Type:
Circuit breakers
Electric Panel Manufacturer:
SQUARE D
Branch wire 15 and 20 AMP:
Copper
Wiring Methods:
Romex

 

IN

NI

NP

RR

6.0

Service Entrance Conductors

6.1

Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels

6.2

Branch Circuit Conductors, Overcurrent Devices and Compatability of their Amperage and Voltage

6.3

Connected Devices and Fixtures (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling’s exterior walls)

6.4

Polarity and Grounding of Receptacles within 6 feet of interior plumbing fixtures, all receptacles in garage, carport and exterior walls of inspected structure

6.5

Operation of GFCI (Ground Fault Circuit Interrupters)

6.6

Operation of AFCI (ARC Fault Circuit Interrupters)

6.7

Location of Main and Distribution Panels

6.8

Smoke Detectors

IN

NI

NP

RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

Comments:

6.1 (1)
The electrical condenser unit disconnect box had knock-outs missing on panel and dead front cover missing. I recommend a licensed electrical contractor inspect further
and correct as needed.

6.1 Item 1 (Picture)
6.1 (2)
The electrical main panel had a thermal anomaly indicating a potential defect. I recommend a licensed electrical contractor inspect further and correct as needed.

6.1 Item 2 (Picture)

6.1 Item 3 (Picture)
6.1 (3)
The electrical sub panel had a thermal anomaly indicating a potential defect. I recommend a licensed electrical contractor inspect further and correct as needed.

6.1 Item 4 (Picture)

6.3 (1)
There were two issues found at the wash machine outlet.

  1. The outlet for the wash machine is wired in to the dryer receptacle and is not separate in the laundry room.
  2. The wash machine outlet is used to supply the light in the laundry room.

The wash machine outlet should be on a separate dedicated circuit. Electrical issues are considered a hazard until repaired. A qualified licensed electrical contractor
should correct as needed.

6.3 Item 1 (Picture)
6.3 (2)
One outlet has partial voltage (30 volts) in the guest bedroom. This is likely due to a loose connection. Further inspection is needed by a qualified licensed electrical
contractor. I recommend repair as needed.

6.3 Item 2 (Picture)
6.5
One GFCI (Ground Fault Circuit Interrupter) outlet at the kitchen wont “trip” when tested. All outlets in wet locations (kitchens, bathrooms, laundry rooms, exterior) should
be GFCI or GFCI protected. A qualified licensed electrical contractor should correct as needed.

6.5 Item 1 (Picture)
6.5 Item 2 (Video)
6.7 (1)
The location of the main panel is on the South exterior wall.

6.7 Item 1 (Picture)
6.7 (2)
The sub panel box is located at the garage.

6.7 Item 2 (Picture)
6.8
The smoke detectors should be tested upon moving in to home. The batteries should be replaced annually and the smoke detector should be replaced every 10 years.
The electrical system of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not accessible (behind the refrigerator for example) was not inspected or accessible. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

7. Insulation and Ventilation

The home inspector shall observe: Insulation and vapor retarders in unfinished spaces; Ventilation of attics and foundation areas; Kitchen, bathroom, and laundry venting systems; and the operation of any readily accessible attic ventilation fan, and, when temperature permits, the operation of any readily accessible thermostatic control. The home inspector shall describe: Insulation in unfinished spaces; and Absence of insulation in unfinished space at conditioned surfaces. The home inspector shall: Move insulation where readily visible evidence indicates the need to do so; and Move insulation where chimneys penetrate roofs, where plumbing drain/waste pipes penetrate floors, adjacent to earth filled stoops or porches, and at exterior doors. The home inspector is not required to report on: Concealed insulation and vapor retarders; or Venting equipment that is integral with household appliances.
Styles & Materials
Attic Insulation:
Blown
Ventilation:
Ridge vents
Soffit Vents
Exhaust Fans:
Fan only
Dryer Power Source:
220 Electric
Dryer Vent:
Flexible Metal
Floor System Insulation:
NONE

 

IN

NI

NP

RR

7.0

Insulation in Attic

7.1

Ventilation of Attic and Foundation Areas

7.2

Venting Systems (Kitchens, Baths and Laundry)

7.3

Ventilation Fans and Thermostatic Controls in Attic

IN

NI

NP

RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

 

The insulation and ventilation of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Venting of exhaust fans or clothes dryer cannot be fully inspected and bends or obstructions can occur without being accessible or visible (behind wall and ceiling coverings). Only insulation that is visible was inspected. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

 

8. Interiors

The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a representative number of installed cabinets; and A representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments.

The inspector shall: Open and close a representative number of doors and windows. Inspect the walls, ceilings, steps, stairways, and railings. Inspect garage doors and garage door openers by operating first by remote (if available) and then by the installed automatic door control. And report as in need of repair any installed electronic sensors that are not operable or not installed at proper heights above the garage door. And report as in need of repair any door locks or side ropes that have not been removed or disabled when garage door opener is in use. And report as in need of repair any windows that are obviously fogged or display other evidence of broken seals.

The inspector is not required to: Inspect paint, wallpaper, window treatments or finish treatments. Inspect central vacuum systems. Inspect safety glazing. Inspect security systems or components. Evaluate the fastening of countertops, cabinets, sink tops and fixtures, or firewall compromises. Move furniture, stored items, or any coverings like carpets or rugs in order to inspect the concealed floor structure. Move drop ceiling tiles. Inspect or move any household appliances. Inspect or operate equipment housed in the garage except as otherwise noted. Verify or certify safe operation of any auto reverse or related safety function of a garage door. Operate or evaluate security bar release and opening mechanisms, whether interior or exterior, including compliance with local, state, or federal standards. Operate any system, appliance or component that requires the use of special keys, codes, combinations, or devices. Operate or evaluate self-cleaning oven cycles, tilt guards/latches or signal lights. Inspect microwave ovens or test leakage from microwave ovens. Operate or examine any sauna, steam-jenny, kiln, toaster, ice-maker, coffee-maker, can-opener, bread-warmer, blender, instant hot water dispenser, or other small, ancillary devices. Inspect elevators. Inspect remote controls. Inspect appliances. Inspect items not permanently installed. Examine or operate any above-ground, movable, freestanding, or otherwise non-permanently installed pool/spa, recreational equipment or self-contained equipment. Come into contact with any pool or spa water in order to determine the system structure or components. Determine the adequacy of spa jet water force or bubble effect. Determine the structural integrity or leakage of a pool or spa.

Styles & Materials
Ceiling Materials:
Drywall
Wall Material:
Drywall
Floor Covering(s):
Tile
Interior Doors:
Hollow core
Raised panel
Wood
Window Types:
Thermal/Insulated
Single-hung
Window Manufacturer:
ANDERSEN
Cabinetry:
Wood
Countertop:
Granite

 

IN

NI

NP

RR

8.0

Ceilings

8.1

Walls

8.2

Floors

8.3

Steps, Stairways, Balconies and Railings

8.4

Counters and Cabinets (representative number)

8.5

Doors (representative number)

8.6

Windows (representative number)

IN

NI

NP

RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

Comments:

8.0
A thermal anomaly was observed on the drywall ceiling in the laundry room below the master bathroom. This is indicative of a past or present leak. The moisture meter was
used and it recorded 19% or higher, which indicates the leak has not been corrected or residual moisture remains in the area. Repairs are needed to prevent water damage
to shower/bath. A qualified person should repair or replace as needed.

8.0 Item 1 (Picture)

8.0 Item 2 (Picture)
8.1
The sheetrock on the wall is damaged at the laundry room. This is a small repair issue for your information. A qualified person should repair or replace as needed.

8.1 Item 1 (Picture)
The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

9. Garage

Styles & Materials
Garage Door Type:
Two automatic
Garage Door Material:
Metal
Auto-opener Manufacturer:
CHAMBERLAIN

 

IN

NI

NP

RR

9.0

Garage Ceilings

9.1

Garage Walls (including Firewall Separation)

9.2

Garage Floor

9.3

Garage Door (s)

9.4

Occupant Door (from garage to inside of home)

9.5

Garage Door Operators (Report whether or not doors will reverse when met with resistance)

IN

NI

NP

RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

Comments:

9.5 (1)
The garage door will reverse when met with resistance.
9.5 Item 1 (Video)
9.5 (2)
The sensors are in place for garage door and will reverse the door.
9.5 Item 2 (Video)

10. Built-In Kitchen Appliances

Styles & Materials
Dishwasher Brand:
GENERAL ELECTRIC
Serial # : ZR785502B
Disposer Brand:
GENERAL ELECTRIC
Serial # : GEGD750A
Range/Oven:
GENERAL ELECTRIC
Serial # : GERE6589878
Built in Microwave:
GENERAL ELECTRIC
Serial # : RR232576A
Refrigerator:
GENERAL ELECTRIC
Serial # : AS327571

 

IN

NI

NP

RR

10.0

Dishwasher

10.1

Ranges/Ovens/Cooktops

10.2

Food Waste Disposer

10.3

Microwave Cooking Equipment

10.4

Refrigerator

IN

NI

NP

RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

Comments:

10.1
The anti-tip bracket for range is missing. An anti-tip bracket is a device that keeps a free standing range from tipping over. They are normally attached to a rear leg of the
range or screwed into the wall behind the range, and are included in all installation kits by the manufacturer. A unit that is not equipped with these devices may tip over if
enough weight is applied to its open door. A falling range can crush, scald, or even burn anyone caught beneath. I recommend repair as needed.

10.1 Item 1 (Picture)

10.1 Item 2 (Picture)
The built-in appliances of the home were inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

11. Lawn Sprinklers

 

IN

NI

NP

RR

11.0

Sprinkler Operation

11.1

Controllers

11.2

Rotary Heads

11.3

Visible Connections or Clamps

11.4

Drains

11.5

Sensors

IN

NI

NP

RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

 

12. Water Wells

Styles & Materials
Pump Type:
Above ground
Accessories:
Air bladder tank
Pump Model Number:
Model Number
Extra Info : GWP57220

 

IN

NI

NP

RR

12.0

Well Pump and Equipment

12.1

Filters and Conditioners

IN

NI

NP

RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

Comments:

12.0
There is a leak at the well pump. The leak will cause the pump to cycle on and off. Repairs by a qualified person is recommended.

12.0 Item 1 (Picture)

13. Septic System

Styles & Materials
Septic Tank:
Not Inspected (Below ground)

 

IN

NI

NP

RR

13.0

Septic Field

13.1

Booster Pump and Alarm

IN

NI

NP

RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

 

14. Photo Video Section

IN NI NP RR
14.0 Additional Photos and Videos
IN NI NP RR

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace

 

Summary

2020 Inspection Solutions5717 Jones Rd.
Saint Cloud Florida 34771
321-877-6247

Customer
John Doe

Address
12345 Sample St
Sample City FL 12345

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the home. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.
1. Roofing
1.0 Roof Coverings
Inspected, Repair or Replace

(1) At the time of inspection the roof covering had excessive granule loss on the entire roof. No active leaks were found. I recommend repair/replace as needed.

1.0 Item 1 (Picture)

1.0 Item 2 (Picture)

(2) The roof covering is missing the vent pipes. Plumbing drain/waste vents are required for proper water flow drainage in the plumbing systems. A qualified contractor should
inspect and repair as needed.

1.0 Item 3 (Picture)
2. Exterior
2.0 Wall Cladding Flashing and Trim
Inspected, Repair or Replace

There were sections of vinyl siding and water barrier house wrap at the rear of home that were missing or incomplete at time of inspection. Deterioration can eventually
occur if not corrected. A qualified person should repair or replace as needed.

2.0 Item 1 (Picture)
5. Plumbing System
5.0 Plumbing Drain, Waste and Vent Systems
Inspected, Repair or Replace

The plumbing waste line for the hall bath tub and hall bath sink leaks in the crawlspace. Repairs are needed to prevent waste water from continuing to leak into crawlspace.
A qualified person should repair as necessary.

5.0 Item 1 (Picture)

5.0 Item 2 (Picture)

5.0 Item 3 (Picture)
5.1 Plumbing Water Supply, Distribution System and Fixtures
Inspected, Repair or Replace

(2) The sink faucet leaks leaks at the master bath. Repairs are needed to stop leaking water from damaging the cabinet bottom. A qualified person should repair as
necessary.

5.1 Item 2 (Picture)
5.1 Item 3 (Video)
6. Electrical System
6.1 Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels
Inspected, Repair or Replace

(1) The condenser unit electrical disconnect box had knock-outs missing on panel and dead front cover missing. I recommend a licensed electrical contractor inspect further
and correct as needed.

6.1 Item 1 (Picture)

(2) The electrical main panel had a thermal anomaly indicating a potential defect. I recommend a licensed electrical contractor inspect further and correct as needed.

6.1 Item 2 (Picture)

6.1 Item 3 (Picture)

(3) The electrical sub panel had a thermal anomaly indicating a potential defect. I recommend a licensed electrical contractor inspect further and correct as needed.

6.1 Item 4 (Picture)
6.3 Connected Devices and Fixtures (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling’s exterior walls)
Inspected, Repair or Replace

(1) There were two issues found at the wash machine outlet.

  1. The outlet for the wash machine is wired in to the dryer receptacle and is not separate in the laundry room.
  2. The wash machine outlet is used to supply the light in the laundry room.

The wash machine outlet should be on a separate dedicated circuit. Electrical issues are considered a hazard until repaired. A qualified licensed electrical contractor
should correct as needed.

6.3 Item 1 (Picture)

(2) One outlet has partial voltage (30 volts) in the guest bedroom. This is likely due to a loose connection. Further inspection is needed by a qualified licensed electrical
contractor. I recommend repair as needed.

6.3 Item 2 (Picture)
6.5 Operation of GFCI (Ground Fault Circuit Interrupters)
Inspected, Repair or Replace

One GFCI (Ground Fault Circuit Interrupter) outlet at the kitchen wont “trip” when tested. All outlets in wet locations (kitchens, bathrooms, laundry rooms, exterior) should
be GFCI or GFCI protected. A qualified licensed electrical contractor should correct as needed.

6.5 Item 1 (Picture)
6.5 Item 2 (Video)
8. Interiors
8.0 Ceilings
Inspected, Repair or Replace

A thermal anomaly was observed on the drywall ceiling in the laundry room below the master bathroom. This is indicative of a past or present leak. The moisture meter was
used and it recorded 19% or higher, which indicates the leak has not been corrected or residual moisture remains in the area. Repairs are needed to prevent water damage
to shower/bath. A qualified person should repair or replace as needed.

8.0 Item 1 (Picture)

8.0 Item 2 (Picture)
8.1 Walls
Inspected, Repair or Replace

The sheetrock on the wall is damaged at the laundry room. This is a small repair issue for your information. A qualified person should repair or replace as needed.

8.1 Item 1 (Picture)
10. Built-In Kitchen Appliances
10.1 Ranges/Ovens/Cooktops
Repair or Replace

The anti-tip bracket for range is missing. An anti-tip bracket is a device that keeps a free standing range from tipping over. They are normally attached to a rear leg of the
range or screwed into the wall behind the range, and are included in all installation kits by the manufacturer. A unit that is not equipped with these devices may tip over if
enough weight is applied to its open door. A falling range can crush, scald, or even burn anyone caught beneath. I recommend repair as needed.

10.1 Item 1 (Picture)

10.1 Item 2 (Picture)
12. Water Wells
12.0 Well Pump and Equipment
Inspected, Repair or Replace

There is a leak at the well pump. The leak will cause the pump to cycle on and off. Repairs by a qualified person is recommended.

12.0 Item 1 (Picture)

 

Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Jay Peters

2020 Inspection Solutions5717 Jones Rd.
Saint Cloud Florida 34771
321-877-6247

Report Attachments

ATTENTION: This inspection report is incomplete without reading the information included herein at these links/attachments. Note If you received a printed version of this page and did not receive a copy of the report through the internet please contact your inspector for a printed copy of the attachments.

Citizens 4-Point Inspection Form with 4 Picture Pages

Florida Wind Mitigation Form – 2012 with 4 Picture Pages

Citizens Roof Inspection Form

HI license 12463

Wind mitigation cert